ENGINEERING HUB
Measure clearly.
Calculate consistently.
Practical SI tools for commissioning checks. Each result shows its assumptions and method so it can be checked against the approved design.
CALCULATOR
Duct run pressure loss
Estimate losses along one constant-area section, then repeat for the other sections on the critical path.
Re = ρvD_h/μ; Δp_straight = f(L/D_h)ρv²/2; Δp_fittings = ΣK × ρv²/2; add known component losses at this flow.
Circular laminar flow uses 64/Re. Turbulent flow uses iterated Colebrook (Re ≥ 4000). Transitional flow and laminar rectangular flow are not estimated. Rectangular turbulent results use a hydraulic-diameter approximation; aspect ratio is limited to 10:1 and roughness/D_h to 0.05.
The pre-filled numbers are illustrative examples. Replace them with measured values or verified project inputs. Calculations do not save data or alter equipment.